108
VmetStatus I/O40
ImetStatus I/O41
I/O: Vmet Status
40 0.00%
I/O: Imet Status
41 0.00%
7 - PARAMETER DESCRIPTION
LCD Display
Range 0% to 100.0% (view only)
Description This parameter contains a value representing the measured voltage at the Vmet (voltage output) terminal as
a percentage of the maximum output voltage. For example, if this parameter showed 50%, then the voltage
being output at Vmet would be 5VDC (50% of 10VDC, the maximum value).
See also I/O 33 on page 104.
LCD Display
Range 0% to 100.0% (view only)
Description This parameter contains a value representing the measured current at the Imet (current output) terminal as a
percentage of the maximum output current. For example, if this parameter showed 50%, then the current
being output at Imet would be 12mA.
See also I/O 33 on page 104.
DOP Scaling I/O 42
I/O: DOP Scaling
42 6FS
LCD Display
Range 6 or 48 times the output frequency (6FS or 48FS) (Default 6FS)
Description This parameter selects the multiplier that is used to determine the output frequency at the DOP (Pulse
Train Output) terminal. The pulse train is a 50% duty cycle signal and requires a pull-up resistor of
approximately 4.7k Ohms.
See also DRV 05, 07 on page 78 and “Description of Control Terminals” on page 41.