Solid State Starter
Control
RediStart
TM
User Manual
RB2, RC2, RX2E Models
Benshaw retains the right to change specifications and illustrations in text without prior notification. The contents of this document may
not be copied without the explicit permission of Benshaw.
2
Seitenansicht 0
1 2 3 4 5 6 ... 221 222

Inhaltsverzeichnis

Seite 1 - RediStart

August 2008Software Version: 810023-01-08Hardware Version: 300055-01-052008 Benshaw Inc.©890034-01-02Solid State StarterControlRediStartT

Seite 2 - Important Reader Notice

1INTRODUCTIONUsing this ManualLayout This manual is divided into 10 sections. Each section contains topics related to the section. The sections are as

Seite 3 - SAFETY PRECAUTIONS

P20 DC Brake Time CFN 19LED Display LCD DisplayRange 1 – 180 Seconds (Default 5)Description When the Stop Mode (P15 / CFN 14) is set to "DC brake

Seite 4 - TABLE OF CONTENTS

936 - PARAMETER DESCRIPTIONP21 DC Brake Delay CFN 20LED Display LCD DisplayRange 0.1 – 3.0 Seconds (Default 0.2)Description When the Stop Mode (P15, C

Seite 5

946 - PARAMETER DESCRIPTIONP24 Ramp Time 2 CFN 05LED Display LCD DisplayRange 0 – 300 seconds (Default 15)Description The Ramp Time 2 parameter sets t

Seite 6

956 - PARAMETER DESCRIPTIONP27 Preset Slow Speed CFN 21LED Display LCD DisplayRange Off, 7.1%, 14.3 % (Default Off)Description The Preset Slow Speed p

Seite 7

966 - PARAMETER DESCRIPTIONP29 Slow Speed Time Limit CFN 23LED Display LCD DisplayRange Off, 1 – 900 Seconds (Default 10)Description The Slow Speed Ti

Seite 8

976 - PARAMETER DESCRIPTIONP31 Slow Speed Kick Time CFN 25LED Display LCD DisplayRange 0.1 – 10.0 seconds (Default 1.0)Description The Slow Speed Kick

Seite 9 - 1 Introduction

986 - PARAMETER DESCRIPTIONJump to Parameter PFN 00By changing the value of this parameter and pressing [ENTER], you can jump directly to any paramete

Seite 10 - 1 - INTRODUCTION

P33 Over Current Trip Delay Time PFN 02LED Display LCD DisplayRange Off, 0.1 – 90.0 seconds (Default 0.1)Description The Over Current Trip Delay Time

Seite 11

1006 - PARAMETER DESCRIPTIONP34 Under Current Trip Level PFN 03LED Display LCD DisplayRange Off, 5 – 100 % of FLA (Default Off)Description If the MX2

Seite 12

1016 - PARAMETER DESCRIPTIONP36 Current Imbalance Trip Level PFN 05LED Display LCD DisplayRange Off, 5 – 40 % (Default 15%)Description The Current Im

Seite 13

Benshaw ServicesGeneral Information Benshaw offers its customers the following:• Start-up services• On-site training services• Technical support• Deta

Seite 14 - RB2-1-S-052A-12C

1026 - PARAMETER DESCRIPTIONP37 Residual Ground Fault Trip Level PFN 06LED Display LCD DisplayRange Off, 5 – 100 % FLA (Default Off)Description The R

Seite 15

P38 Over Voltage Trip Level PFN 07LED Display LCD DisplayRange Off, 1 – 40 % (Default Off)Description If the MX2 detects a one cycle input phase volt

Seite 16

P40 Over/Under Voltage Trip Delay Time PFN 09LED Display LCD DisplayRange 0.1 – 90.0 seconds (Default 0.1)Description The Voltage Trip Delay Time para

Seite 17 - 2 Technical Specifications

P43 Controlled Fault Stop Enable PFN 12LED Display LCD DisplayRange Off – On (Default On)Description A Controlled Fault Stop Enable can occur if thi

Seite 18 - 2 - TECHNICAL SPECIFICATIONS

P44 Independent Starting/Running Overload PFN 13LED Display LCD DisplayRange Off – On (Default Off)Descri

Seite 19

P45 Motor Overload Class Starting PFN 14LED Display LCD DisplayRange Off, 1 – 40 (Default class 10)Description The Motor Overload Class Starting para

Seite 20

P46 Motor Overload Hot/Cold Ratio PFN 16LED Display LCD DisplayRange 0 – 99% (Default 60%)Description The Motor Overload Hot/Cold Ratio parameter defi

Seite 21

P47 Motor Overload Cooling Time PFN 17LED Display LCD DisplayRange 1.0 – 999.9 minutes (Default 30.0)Description The Motor Overload Cooling Time param

Seite 22

1106 - PARAMETER DESCRIPTION Jump to Parameter I/O 00By changing the value of

Seite 23

1116 - PARAMETER DESCRIPTIONP51 Digital Fault Input Trip Time I/O 04LED Display LCD DisplayRange 0.1-90.0 Seconds (Default 0.1 Sec)Description: The D

Seite 24

Contacting BenshawContacting Benshaw Information about Benshaw products and services is available by contacting Benshaw at one of thefollowing offices

Seite 25

1126 - PARAMETER DESCRIPTIONP52, 53, 54 Relay Output Configuration I/O 05, 06, 07 LED Display LCD DisplayRangeLED LCD DescriptionOFF Of

Seite 26

P55 Analog Input Trip Type I/O 08LED Display LCD DisplayRange LED LCD DescriptionOFF Off Off, Disabled. (Default)Lo Low Level Low, Fault if input sign

Seite 27

1146 - PARAMETER DESCRIPTIONP56 Analog Input Trip Level I/O 09LED Display LCD DisplayRange 0 – 100% (Default 50%)Description The Analog Input Trip Lev

Seite 28

1156 - PARAMETER DESCRIPTIONP58 Analog Input Span I/O 11LED Display LCD DisplayRange 1 – 100% (Default 100%)Description The analog input can be scaled

Seite 29

1166 - PARAMETER DESCRIPTIONP59 Analog Input Offset I/O 12LED Display LCD DisplayRange 0 – 99% (Default 0%)Description The analog input can be offset

Seite 30

P61 Analog Output Span I/O 14LED Display LCD DisplayRange 1 – 125% (Default 100%)Description The analog output signal can be scaled using the Analog O

Seite 31

1186 - PARAMETER DESCRIPTIONP63 Inline Configuration I/O 16LED Display LCD DisplayRange Off, 0 – 10.0 seconds (Default 3.0)Description The Inline Conf

Seite 32

1196 - PARAMETER DESCRIPTIONP65 Keypad Stop Disable I/O 18LED Display LCD DisplayRange LED LCD DescriptionOFF Disabled Keypad Stop does not stop the s

Seite 33

1206 - PARAMETER DESCRIPTIONJump to Parameter FUN 00By changing the value of this parameter and pressing [ENTER], you can jump directly to any paramet

Seite 34

P68 Communication Timeout FUN 12LED Display LCD DisplayRange Off, 1 – 120 seconds (Default Off)Description The Communication Timeout parameter sets th

Seite 35 - 3 Installation

MX2 & MX3 Product Comparison1.1 Additional MX3 Product FeaturesThe MX2 is a standard solid state starter. If you require additional features, plea

Seite 36 - 3 - INSTALLATION

1226 - PARAMETER DESCRIPTIONP71 Communication Byte Framing FUN 13LED Display LCD DisplayRange LED LCD0 Even, 1 Stop (Default)1 Odd, 1 Stop2 None, 1 St

Seite 37

P73 Heater Level FUN 08LED Display LCD DisplayRange Off, 1 – 25% FLA (Default Off)Description The Heater Level parameter sets the level of D.C. curren

Seite 38

P74 Starter Type FUN 07LED Display LCD DisplayRange LED LCD Descriptionnor Normal Normal Reduced Voltage Soft Starter RVSS. (Default)I d Inside Delta

Seite 39

1256 - PARAMETER DESCRIPTIONP75 Motor Rated Power Factor FUN 06LED Display LCD DisplayRange -0.01 – 1.00 (Default –0.92)Description The Rated Power Fa

Seite 40 - BIPC-300055-01

P77 Input Phase Sensitivity FUN 04LED Display LCD DisplayRange LED LCD DescriptionInS Insensitive Runs with any three phase sequence. (De

Seite 41

P79 Meter 1 ,Meter 2 FUN 01, 02LED Display LCD DisplayRange LED LCD Description0 Status Running State. (LED meter only, Default LED meter)1 Ave Curren

Seite 42

P80 Software 1 FUN 14LED Display LCD DisplayDescription The Software Part Number parameter displays the MX2 software version, for hardware BIPC-300055

Seite 43

P81 Passcode FUN 16LED Display LCD DisplayDescription The MX2 supports a 4-digit passcode. When the passcode is set, parameters may not be changed.Th

Seite 44

P82 Fault Log FL1LED Display LCD DisplayRange FL1 – FL9Description When a fault occurs, the fault number is logged in non-volatile memory. The most r

Seite 45

7 Theory of Operation

Seite 46

Interpreting Model NumbersExample of Model Number: RX2-1S-361A-14CA RediStart starter with bypass, MX2 control, Integrated Bypass, Standard Fault, 361

Seite 47

7THEORY OF OPERATIONMotor Overload7.1 Solid State Motor Overload Protection7.1.1 OverviewThe MX2 contains an advanced I2t electronic motor overload (O

Seite 48 - 120VAC NEUTRAL

z NOTE: In some cases the power stack rating may determine what motor overload settings are available. Each power stack isdesigned to support specif

Seite 49

7.1.3 Motor Overload OperationOverload HeatingWhen the motor is operating in the overloaded condition (motor current greater than FLAxSF), the motor o

Seite 50

7.1.5 Harmonic CompensationThe MX2 motor overload calculation automatically compensates for the additional motor heating that can result from the pres

Seite 51

The following diagram illustrates how the current and the Motor Overload Hot/Cold Ratio parameter determines the steady stateoverload content. It ass

Seite 52

7.1.8 Motor Cooling While StoppedThe Motor Overload Cooling Time parameter is used to adjust the cooling rate of the motor overload. When the motor i

Seite 53

If the motor manufacturer does not specify the motor cooling time, the following approximations for standard TEFC cast iron motorsbased on frame size

Seite 54

Motor Service Factor7.2 Motor Service FactorGeneral The Motor Service Factor parameter should be set to the service factor of the motor. The service

Seite 55 - 4 Keypad Operation

Acceleration Control7.3 Acceleration Control7.3.1 Current Ramp Settings, Ramps and TimesGeneral The current ramp sets how the motor accelerates. The

Seite 56 - PARAM DOWN UP ENTERRESET

Ramp Time The ramp time is the time it takes for the current to go from the initial current to the maximum current. Tomake the motor accelerate faste

Seite 57 - 4 - KEYPAD OPERATION

General Overview of a Reduced Voltage StarterGeneral Overview The RediStart MX2 motor starter is a microprocessor-controlled starter for single or thr

Seite 58

1427 - THEORY OF OPERATIONTruTorque acceleration control can be very useful for a variety of applications. However it is best used tostart centrifuga

Seite 59

7.3.4 Power Control Acceleration Settings and TimesGeneral Power control is a closed loop power based acceleration control. The primary purpose of Po

Seite 60

z NOTE: Depending on loading, the motor may achieve full speed at any time during the Power ramp. Thismeans that the Maximum Power level may not be r

Seite 61

1457 - THEORY OF OPERATION7.3.5 Open Loop Voltage Ramps and TimesGeneral The open loop voltage ramp provides soft starting of a motor by increasing th

Seite 62

UTS Timer When the start mode is set to open-loop voltage ramp acceleration, the UTS Timer acts as an accelerationkick. When the UTS timer expires, f

Seite 63

7.3.6 Dual Acceleration Ramp ControlGeneral Two independent current ramps and kick currents may be programmed. The use of two different startingprofi

Seite 64

1487 - THEORY OF OPERATIONChanging Ramp Profiles The selected ramp profile may be changed during starting by changing the Ramp Select input. When the

Seite 65

Deceleration Control7.4 Deceleration Control7.4.1 Voltage Control DecelerationOverview The deceleration control on the MX2 uses an open loop voltage r

Seite 66

7.4.2 TruTorque DecelerationOverview TruTorque deceleration control is a closed loop deceleration control. This allows TruTorque deceleration tobe mo

Seite 67 - 5 Parameter Groups

Braking Controls7.5 Braking ControlsOverview When the Stop Mode parameter is set to DC Brake, the MX2 starter provides DC injection braking for fast a

Seite 68 - 5 - PARAMETER GROUPS

NOTES:81 - INTRODUCTION

Seite 69

1527 - THEORY OF OPERATION7.5.1 DC Injection Braking, Standard DutyThe MX2 Standard Duty Braking allows up to approximately 250% FLA current to be app

Seite 70

7.5.5 DC Injection Brake Wiring Example1537 - THEORY OF OPERATIONSTARTStartersstopresetentermenuMX2 CARDBIPC-300055-01Figure 37: DC Injection Brake Wi

Seite 71

7.5.6 DC Brake TimingThe MX2 DC injection brake timing is shown below:After the DC Brake Time has expired, the Braking Relay is held energized to allo

Seite 72

7.5.7 DC Injection Brake Enable and Disable Digital InputsDigital inputs can be programmed to either a Brake Enable or a Brake Disable. In the Brake

Seite 73

7.5.9 DC Injection Braking ParametersBrake Level: The DC Brake Level parameter sets the level of DC current applied to the motor during braking. The

Seite 74

7.6.2 Slow Speed Cyclo Converter ParametersSlow Speed: The Slow Speed parameter selects the speed of motor operation when slow speed is selected. Whe

Seite 75

Inside Delta Connected Starter7.7 Inside Delta Connected StarterThere are differences between a line connected soft starter as shown in Figure 39 and

Seite 76

7.7.2 Inside Delta Connected StarterAn inside delta connected soft starter is shown in Figure 40, where the power poles are connected in series with t

Seite 77

Wye Delta Starter7.8 Wye Delta StarterWhen the Starter Type parameter is set to Wye-Delta, the MX2 is configured to operate an Electro mechanical Wye-

Seite 78

The MX2 utilizes an intelligent Wye to Delta transition algorithm. During starting, if the measured motor current drops below 85% ofFLA and more than

Seite 79

2 Technical Specifications

Seite 80

Usually the MX2 intelligent Wye to Delta transition algorithm provides an optimal transition point that minimizes the transient currentand torque surg

Seite 81 - 6 Parameter Description

Across The Line Starter7.9 Across The Line (Full Voltage Starter)When the Starter Type parameter is set to ATL, the MX2 is configured to operate an El

Seite 82

Single Phase Soft Starter7.10 Single Phase Soft StarterThere are times a single phase motor may need to be started using a soft starter. This can be a

Seite 83

Phase Control7.11 Phase ControlWhen the Starter Type parameter is set to Phase Control, the MX2 is configured to operate as a phase controller or volt

Seite 84

7.11.1 Master/Slave Starter Configuration:In the master / slave configuration, one "master" starter can directly control the output of one o

Seite 85

Current Follower7.12 Current FollowerWhen the Starter Type parameter is set to Current Follower, the MX2 is configured to operate as a Closed Loop cur

Seite 86 - P48, P49, P50

Start/Stop Control with a Hand/Off/Auto Selector Switch7.13 Start/Stop Control LogicOften times, a switch is desired to select between local or “Hand”

Seite 87

1697 - THEORY OF OPERATION7.14 Hand/Off/Auto Selector SwitchThe MX2 has the capability to use a selector switch to change the source of control. A pop

Seite 88

1707 - THEORY OF OPERATIONSimplified I/O Schematics7.15 Simplified I/O SchematicsFigure 50: Analog Output Simplified SchematicFigure 49: Analog Input

Seite 89

Remote Modbus Communications7.16Remote Modbus CommunicationsThe MX2 starter provides a Modbus RTU to support remote communication.The communication in

Seite 90

2TECHNICAL SPECIFICATIONSTechnical Specifications2.1 General InformationThe physical specifications of the starter vary depending upon its configurati

Seite 91

7.16.41727 - THEORY OF OPERATIONIMPORTANTDO NOT CREATE STUBS - CABLEMUST GO TO EACH STARTER.RightWrongFigure 50: Modbus Network Wiring Example

Seite 92

8Troubleshooting& Maintenance

Seite 93

8TROUBLESHOOTING & MAINTENANCESafety Precautions8.1 Safety PrecautionsFor safety of maintenance personal as well as others who might be exposed to

Seite 94

General Troubleshooting Charts8.3 General Troubleshooting ChartsThe following troubleshooting charts can be used to help solve many of the more common

Seite 95

8.3.2 During starting, motor rotates but does not reach full speed8.3.3 Starter not accelerating as desired1768 - TROUBLESHOOTING & MAINTENANCECo

Seite 96

8.3.4 Starter not decelerating as desired8.3.5 Motor stops unexpectedly while running1778 - TROUBLESHOOTING & MAINTENANCEConditionCause SolutionMo

Seite 97

8.3.6 Metering incorrect1788 - TROUBLESHOOTING & MAINTENANCECondition Cause SolutionPower Metering not reading correctly. CTs installed or wired i

Seite 98

8.3.7 Other Situations1798 - TROUBLESHOOTING & MAINTENANCECondition Cause SolutionMotor Rotates in Wrong Direction. Phasing incorrect. If input p

Seite 99

Fault Code Table8.4 Fault Code TableThe following is a list of possible faults that can be generated by the MX2 starter control.1808 - TROUBLESHOOTING

Seite 100 - 6 - PARAMETER DESCRIPTION

1818 - TROUBLESHOOTING & MAINTENANCEFault Code Description Detailed Description of Fault / Possible SolutionsF13 High Line Frequency Line frequenc

Seite 101

2.2.2 Measurements and Accuracies2.2.3 List of Motor Protection Features• ANSI 19 – Reduced Voltage Start• ANSI 27 / 59 – Adjustable over/under voltag

Seite 102

1828 - TROUBLESHOOTING & MAINTENANCEFault Code Description Detailed Description of Fault / Possible SolutionsF24 High Line L1-L2 High voltage abov

Seite 103

1838 - TROUBLESHOOTING & MAINTENANCEFault Code Description Detailed Description of Fault / Possible SolutionsF30 I.O.C.(Instantaneous Over current

Seite 104

1848 - TROUBLESHOOTING & MAINTENANCEFault Code Description Detailed Description of Fault / Possible SolutionsF40 Shorted / Open SCR A shorted or o

Seite 105

1858 - TROUBLESHOOTING & MAINTENANCEFault Code Description Detailed Description of Fault / Possible SolutionsF51 Current Sensor Offset Error Indic

Seite 106

F82 Modbus Timeout Fault Indicates that the starter has lost serial communications. Fault occurs when the starter has not received a valid serialcomm

Seite 107

SCR Testing8.5 SCR Testing8.5.1 ResistanceThe SCRs in the starter can be checked with a standard ohmmeter to determine their condition.Remove power fr

Seite 108 - % Current

Built-In Self Test Functions8.6 Built In Self Test FunctionsThe MX2 has two built in self test (BIST) modes. The first test is the standard self test

Seite 109

z NOTE: If one dedicated bypass is set to "fan" and if no digital input are assigned as a Bypass Confirm input, this test will alwayspass

Seite 110

z NOTE: The motor wiring MUST be fully connected before starting the powered BIST tests. Also the motor must be at rest(stopped). Otherwise the pow

Seite 111

SCR Replacement8.7 SCR ReplacementThis section is to help with SCR replacements on stack assemblies. Please read prior to installation.8.7.1 Typical

Seite 112

TRADEMARK NOTICEBenshaw and are registered trademarks of Benshaw Incorporated.UL is a trademark of Underwriters Laboratories, Incorporated.Important

Seite 113

2.2.4 Solid State Motor OverloadThe MX2 control has an advanced I2t electronic motor overload (OL) protection function. For optimal motor protection

Seite 114

8.7.4 SCR ClampBelow is an exploded view of a typical SCR clamp. Refer to the Clamp Parts List below for names of the parts being used. SCR CL

Seite 115

Appendices

Seite 116

APPENDIX AALARM CODESAlarm CodesThe following is a list of all MX2 alarm codes. The alarm codes correspond to associate fault codes. In general, an

Seite 117

195APPENDIX A - ALARM CODESAlarmCodeDescription NotesA38 Ground FaultThis alarm exists while the MX2 is running and a groundcurrent above the defined

Seite 118

APPENDIX BFAULT CODESFault Codes196APPENDIX B - FAULT CODESFault Code Description Controlled Fault Stop Shunt Trip Fault Auto-Reset AllowedF00 No faul

Seite 119

APPENDIX CSPARE PARTSOptions and AccessoriesSpare PartsAPPENDIX D197APPENDIX C - SPARE PARTSDescription Part Number Size1) LCD Display (small) KPMX3SL

Seite 120

EU DECLARATION OF CONFORMITYEU Declaration of ConformityAccording to the EMC – Directive 89/336/EEC as Amended by 92/31/EEC and 93/68/EECProduct Categ

Seite 121

APPENDIX EMODBUS REGISTER MAPModbus Register MapFollowing is the Modbus Register Map. Note that all information may be accessed either through the In

Seite 122

200APPENDIX E - MODBUS REGISTER MAPAbsolute Register Address Description Range Units30026/40026 Lockout StatusBit 0: “L OL” – Motor overloadBit 1:

Seite 123

201APPENDIX E - MODBUS REGISTER MAPAbsolute Register Address Description Range Units30104/40104 Motor Overload Running Enable0: Disabled1: Enabled-301

Seite 124

2.2.5 CT Ratiosz NOTE: See P78/FUN 03 (CT Ratio) parameter on page 126 for more information.Starter Power Ratings2.3 Starter Power RatingsEach RB2 mod

Seite 125

202APPENDIX E - MODBUS REGISTER MAPAbsolute Register Address Description Range Units30143/40143 Rated RMS Voltage0: 1001: 1102: 1203: 2004: 2085: 2206

Seite 126

203APPENDIX E - MODBUS REGISTER MAPAbsolute Register Address Description Range Units30168/40168 Controlled Fault Stop0: Disabled1: Enabled-30169/40169

Seite 127

204APPENDIX E - MODBUS REGISTER MAPAbsolute Register Address Description Range Units30184/40184 Inline Enable0: Disabled1: Enabled-30185/40185 Inline

Seite 128

205APPENDIX E - MODBUS REGISTER MAPAbsolute Register Address Description Range Units30197/40197LCD Display Meter 11: Ave Current2: L1 Current3: L2 Cur

Seite 129

Diagnostics These registers provide some diagnostics capabilities for testing and controlling the communications link. 206AP

Seite 130

The control source must be serial for the starter to be started through Modbus. The Run/Stop bit must transition from 0 to 1 for a start tooccur. If

Seite 131

Parameter TableFollowing is the parameter table for both the LED and LCD Display. The last column is a convenient place to write down parametersettin

Seite 132

Protection Function GroupI/O Group209APPENDIX F - PARAMETER TABLESLED LCD Parameter Setting Range Units Default Page SettingP32 PFN 01 Over Current Le

Seite 133

210APPENDIX F - PARAMETER TABLESLED LCD Parameter Setting Range Units Default Page SettingP52 I/O 05R1 ConfigurationOFF: OffFLFS: Fault (fail safe)FLn

Seite 134

Function Group211APPENDIX F - PARAMETER TABLESLED LCD Parameter Setting Range Units Default Page SettingP79 FUN 01 Meter 10: Status1: Ave Current2: L1

Seite 135

2.3.1 Standard Duty (350% for 30 sec) Ratingsz NOTE: Do not exceed Class 10 overload setting.142 - TECHNICAL SPECIFICATIONSStandard Duty (350% curren

Seite 136

LCD Fault Group212APPENDIX F - PARAMETER TABLESGroupFault NumberFault DescriptionStarterStateI1 I2 I3 V1 V2 V3 kW HzRunTimeFL1FL2FL3FL4FL5FL6FL7FL

Seite 137

Publication History;Revision Date ECO#00 12/15/06 Initial Release01 09/10/0702 08/21/08Revisions based onshared review

Seite 138

BENSHAW615 Alpha DrivePittsburgh, PA 15238Phone: (412) 968-0100Fax: (412) 968-5415BENSHAW Canada550 Bright StreetListowel, Ontario N4W 3W3Phone:

Seite 139 - 7 Theory of Operation

2.3.2 Heavy Duty (500% current for 30 sec) Ratingsz NOTE: Do not exceed Class 20 overload setting.152 - TECHNICAL SPECIFICATIONSHeavy Duty (500% curre

Seite 140 - 7 - THEORY OF OPERATION

2.3.3 Severe Duty (600% current for 30 sec) Ratingsz NOTE: Do not exceed Class 30 overload setting.162 - TECHNICAL SPECIFICATIONSSevere Duty (600% cu

Seite 141

2.3.4 Inside Delta Connected Standard Duty (350% for 30 sec) Ratingsz NOTE: Do not exceed Class 10 overload setting.172 - TECHNICAL SPECIFICATIONSINSI

Seite 142 - Derating Factor

2.3.5 RB2 Power Stack Ratings and Protection Requirements182 - TECHNICAL SPECIFICATIONSrebmuN ledoMlanimoNtnerruC)A(%511tnerruCgnitaR)A(lanimoN)A( tne

Seite 143

2.3.6 Power Stack Input Ratings with Protection Requirements for Separate Bypass192 - TECHNICAL SPECIFICATIONSrebmuN ledoMlanimoNtnerruC)A(%511 tnerru

Seite 144

2.3.7 Power Stack Input Ratings with Protection Requirements for RC No Bypass202 - TECHNICAL SPECIFICATIONSrebmuN ledoMlanimoNtnerruC)A(%521tnerruCtin

Seite 145

2.3.8 RB2 Starter Control Power Requirements2.3.9 RC2 Starter Control Power Requirements212 - TECHNICAL SPECIFICATIONSModel NumberPowerRequired(VA)Rec

Seite 146

Safety PrecautionsElectric Shock Prevention• While power is on or soft starter is running, do not open the front cover. You may get an electrical shoc

Seite 147

Mechanical Drawings2.4 Dimensions2.4.1 RB2 Chassis with Integral Bypass222 - TECHNICAL SPECIFICATIONSFigure 3: RB2 - 27A - 96A ModelA B C D E F RB2

Seite 148

232 - TECHNICAL SPECIFICATIONSFigure 5: RB2 414 - 838A ModelA B C D ERB2 414-590A27.66 18.5 26.25 6 0.31RB2 720A 29.38 18.5 28 6 0.31RB2 838A 27.75 2

Seite 149

2.4.2 RC2 Chassis with no Bypass242 - TECHNICAL SPECIFICATIONSFigure 6: RC2 0 - 124A ModelA B C D ERC2 27-52A14 9.875 3.375 4.69 8-32 TAPRC2 65-77A18

Seite 150

Environmental Conditions2.5 Environmental Con

Seite 151

Approvals2.7 ApprovalsMX2 Control Card is UL, cUL RecognizedCertificate of Compliance2.8 Certificate of ComplianceCE Mark, See Appendix D on page 198.

Seite 152

3 Installation

Seite 153

3INSTALLATIONBefore You Start3.1 Before You Start3.1.1 InspectionBefore storing or installing the RediStart MX2 Series Starter, thoroughly inspect the

Seite 154

Installation Considerations3.2 Installation Considerations3.2.1 Site PreparationGeneral InformationBefore the starter can be installed, the installati

Seite 155

Mounting Considerations3.3 Mounting Considerations3.3.1 Bypassed StartersProvisions should be made to ensure that the average temperature inside the e

Seite 156 - Ramp Profile 1

313 - INSTALLATIONWiring Considerations3.4 Wiring Considerations3.4.1 Wiring PracticesWhen making power and control signal connections, the following

Seite 157

Table of Contents1 INTRODUCTION ...21.1 Additional MX3 Product Features...

Seite 158

323 - INSTALLATIONPower and Control Drawings for Bypassed and Non Bypassed Power Stacks3.5 Power and Control drawings for Bypassed and Non Bypassed Po

Seite 159

333 - INSTALLATIONSTARTStartersstopresetentermenuMX2 CARDBIPC-300055-01Figure 9: Power Schematic for RB2 High HP

Seite 160

343 - INSTALLATIONSTARTStartersstopresetentermenuMX2 CARDBIPC-300055-01Figure 10: Power Schematic for RC2

Seite 161

353 - INSTALLATIONPower Wiring3.6 Power Wiring3.6.1 Recommended Incoming Line ProtectionFuses or Circuit Breaker, refer to pages 18 - 20.Input Line Re

Seite 162

3.6.5 Compression LugsThe following is a list of the recommended crimp-on wire connectors manufactured by Penn-Union Corp. for copper wire.363 - INSTA

Seite 163

3.6.6 Torque Requirements for Power Wiring Terminations373 - INSTALLATIONWire size installed in conductorTightening torque, pound-inches (N-m)Slotted

Seite 164

383 - INSTALLATIONCurrent Transformers3.7 Current Transformers3.7.1 CT MountingFor starters larger than 124 amps, the CTs are shipped loose from the p

Seite 165

393 - INSTALLATIONControl Card Layout3.8 Control Card LayoutABCDEFGH1 2 3 4 5 6Unfused120 VAC OutControlPower120 VACAuxiliaryRelaysP52-54I/O 5-7Digita

Seite 166

Control Wiring3.9 Control Wiring3.9.1 Control PowerThe 120VAC control power is supplied to TB1. The connections are as follows:1 - Ground2 - Neutral3

Seite 167

3.9.3 Digital Input Wiring OptionsTB3 is for the digital inputs. The digital inputs use 120VAC. The digital inputs are as follows:1 - Start: Start Inp

Seite 168

3.6 Power Wiring ...353.6.1 Recommended Incoming Line Protection ...353.6.

Seite 169

423 - INSTALLATION3.9.4 Analog InputThe analog input can be configured for voltage or current loop. The input is shipped in the voltage loop configura

Seite 170

3.9.6 SW1 DIP SwitchThe DIP switch on the card changes the analog input and analog output between 0-10V or 0-20mA. The picture below shows how to adju

Seite 171

443 - INSTALLATION3.10.2 Display Cutout50.50[1.99"]50.50[1.99"]31.50[1.24"]31.50[1.24"]101.00[3.98"]63.00[2.48"]Figure 1

Seite 172

3.10.3 Installing DisplayThe remote display is installed as follows:• Install the gasket onto the display.• Insert the display through the door cutout

Seite 173

NOTES:463 - INSTALLATION

Seite 174

4 Keypad Operation

Seite 175

4KEYPAD OPERATIONIntroduction4.1 IntroductionThe MX2 provides a comprehensive set of parameters to allow the use of the reduced voltage solid state st

Seite 176

Changing Parameter Values4.4 Changing Parameter ValuesParameter change mode can be entered by:1. At the default meter display, press the [PARAM] key t

Seite 177

4.5.3 RunningWhen running, the display shows the selected meter function. The following meters can be selected using the Meter display parameter(P79)

Seite 178

Restoring Factory Parameter Settings4.6 Restoring Factory Parameter SettingsTo restore ALL parameters to the factory default settings, press and hold

Seite 179

5 PARAMETER GROUPS...605.1 Introduction ...605.2 LED and LCD Dis

Seite 180 - IMPORTANT

524 - KEYPAD OPERATIONRemote LCD Keypad and Display4.9 2x16 Remote LCD KeypadLike the standard keypad, the remote LCD keypad has the same basic functi

Seite 181 - & Maintenance

Description of the Keys on the Remote LCD Keypad4.11 Description of the Keys on the Remote LCD KeypadThe [UP] arrow, [DOWN] arrow, [ENTER] and [MENU]

Seite 182 - Preventative Maintenance

Jump Code4.12 Jump CodeAt the beginning of each parameter group, there is a Jump Code parameter. By changing the value of this parameter and pressing

Seite 183 - control

554 - KEYPAD OPERATION4.13.1 Parameter Group ScreensFrom the operate screen, the parameter group screens are accessed by pressing either the menu or t

Seite 184 - . Initial current to low

4.13.2 Meter PagesAlthough any meter may be viewed by changing the two Meter parameters (FUN 01 & FUN 02), there are 13 “Meter Pages” that areeasi

Seite 185 - Condition

574 - KEYPAD OPERATIONPress [MENU] until you get to the FL1 parameter.Pressing the [UP] and [DOWN] keys navigates through older and newer faults in th

Seite 186

Procedure for Setting Data4.14 Procedure for Setting DataSelect a parameter that is to be changed. To change Motor FLA from 10 Amps to 30 Amps:From t

Seite 187

5 Parameter Groups

Seite 188 - Fault Code Table

5PARAMETER GROUPSIntroduction5.1 IntroductionThe MX2 incorporates a number of parameters that allow you to configure the starter to meet the special r

Seite 189

615 - PARAMETER GROUPSLED & LCD Display Parameters Cross Reference5.2 LED and LCD Display Parameters Cross ReferenceParameter NumberGroup Paramete

Seite 190

7.8 Wye Delta Starter ...1607.9 Across The Line (Full Voltage Starter) ...16

Seite 191

LED Display Parameters5.3 LED Display Parameters625 - PARAMETER GROUPSNumber Parameter Setting Range Units Default PageP1 Motor FLA 1 – 6400 RMS Amps

Seite 192

635 - PARAMETER GROUPSNumber Parameter Setting Range Units Default PageP41 Auto Fault Reset Time Off, 1 – 900 Seconds Off 104P42 Auto Reset Limit Off,

Seite 193

645 - PARAMETER GROUPSNumber Parameter Setting Range Units Default PageP60 Analog Output Function0: Off (no output)1: 0 – 100% Curr2: 0 – 200% Curr

Seite 194

655 - PARAMETER GROUPSNumber Parameter Setting Range Units Default PageP78 CT Ratio72:1, 96:1, 144:1, 288:1,864:1, 2640:1, 3900:1,5760:1, 8000:1, 1440

Seite 195 - SCR Testing

LCD Display Parameters5.4 LCD Display ParametersThe 2x16 display has the same parameters available as the LED display, with the exception of two meter

Seite 196 - Built-In Self Test Functions

5.4.2 Control Function Group675 - PARAMETER GROUPSNumber Display Parameter Setting Range Units Default PageCFN 00 Jump Code Jump to Parameter 1 to 25

Seite 197 - Tests completed

5.4.3 Protection Group5.4.4 I/O Group685 - PARAMETER GROUPSNumber Display Parameter Setting Range Units Default PagePFN 00 Jump Code Jump to Parameter

Seite 198

695 - PARAMETER GROUPSNumber Display Parameter Setting Range Units Default PageI/O 05 R1 Config R1 Configuration (Relay #1) OffFault FS (Fail Safe)Fau

Seite 199 - SCR Replacement

5.4.5 Function Group705 - PARAMETER GROUPSNumber Display Parameter Setting Range Units Default PageFUN 00 Jump Code Jump to parameter 1 to 16 1 120FUN

Seite 200

5.4.6 LCD Fault Group5.4.7 LED Fault Group715 - PARAMETER GROUPSNumber Display Parameter Setting Range Units Default PageFUN 13 Com Parity Communicati

Seite 201 - Appendices

APPENDIX A ALARM CODES ...194APPENDIX B FAULT CODES ...196APPENDIX C SPARE PAR

Seite 202 - APPENDIX A - ALARM CODES

NOTES:725 - PARAMETER GROUPS

Seite 203

6 Parameter Description

Seite 204 - APPENDIX B - FAULT CODES

6PARAMETER DESCRIPTIONParameter Descriptions6.1 Parameter DescriptionsThe detailed parameter descriptions in this chapter are organized in the same or

Seite 205 - APPENDIX C - SPARE PARTS

Jump to Parameter QST 00By changing the value of this parameter and pressing [ ENTE

Seite 206 - EU DECLARATION OF CONFORMITY

P3 Motor Overload Class Running QST 03, PFN 15LED Display LCD DisplayRange Off, 1– 40 (Default 10)Description The Motor Running Overload

Seite 207 - APPENDIX EMODBUS REGISTER MAP

P4 Local Source QST 04LED Display LCD DisplayRange LED LCD DescriptionPAd Keypad The start/stop control is from the keypad.tEr Terminal The start/stop

Seite 208

P5 Remote Source QST 05LED Display LCD DisplayRange LED LCD DescriptionPAd Keypad The start/stop control is from the keypad.tEr Terminal The start/sto

Seite 209

796 - PARAMETER DESCRIPTIONP6 Initial Motor Current 1 QST 06, CFN 03LED Display LCD DisplayRange 50 – 600 % of FLA (Default 100%)Desc

Seite 210

P7 Maximum Motor Current 1 QST 07, CFN 04LED Display LCD DisplayRange 100 – 800 % of FLA (Default 600%) Description The Maximum Motor Curren

Seite 211 - 0 – 99 %

P8 Ramp Time 1 QST 08, CFN 02LED Display LCD DisplayRange 0 – 300 seconds (Default 15)Description The Ramp Time 1 pa

Seite 212

1 Introduction1

Seite 213

826 - PARAMETER DESCRIPTIONP9 Up To Speed Time QST 09LED Display LCD DisplayRange 1– 900 Seconds (Default 20)Description The Up To Speed Time paramete

Seite 214 - Diagnostics

Jump to Parameter CFN 00By changing the value of this parameter and pressing [

Seite 215 - APPENDIX FPARAMETER TABLES

P11 Initial Voltage/Torque/Power CFN08LED Display LCD DisplayRange 1 – 100 % of Voltage/Torque/Power (Default 25%)Description Start Mode (P10/CFN01) s

Seite 216 - APPENDIX F - PARAMETER TABLES

P12 Maximum Torque/Power CFN 09LED Display LCD DisplayRange 10 – 325 % of Torque/Power (Default 105%)Description Start Mode (P10/CFN01) set to Open L

Seite 217

866 - PARAMETER DESCRIPTIONP13 Kick Level 1 CFN 10LED Display LCD DisplayRange Off, 100 – 800% of FLA (Default Off)Description The Kick Level 1 parame

Seite 218

P15 Stop Mode CFN 14LED Display LCD DisplayRange LED LCD DescriptionCoS Coast Coast to stop. (Default)SdcL Volt Decel Open loop voltage deceleration.t

Seite 219

886 - PARAMETER DESCRIPTIONP16 Decel Begin Level CFN 15LED Display LCD DisplayRange 1 % – 100% of phase angle firing (Default 40%)Description Stop Mod

Seite 220

896 - PARAMETER DESCRIPTIONP17 Decel End Level CFN 16LED Display LCD DisplayRange 1 – 99 % of phase angle firing (Default 20%)Description Stop Mode (P

Seite 221 - Publication History;

906 - PARAMETER DESCRIPTIONP18 Decel Time CFN 17LED Display LCD DisplayRange 1 – 180 seconds (Default 15)Description The Decel Time parameter sets the

Seite 222

P19 DC Brake Level CFN 18LED Display LCD DisplayRange 10 – 100 % of available brake torque (Default 25%)Description When the Stop Mode (P15 / CFN 14)